PTS-200(F) face
Specifications
Input:120V, 60Hz, 15A or 230V, 50/60Hz, 8A
Output:0 - 200kVdc, 5mA, negative polarity, positive ground
Duty:Continuous
Metering
Voltmeter:3.5", scaled 0-80/200kVdc, ±2% FS accuracy
Currentmeter:3.5", scaled 0-1.0µAdc, ±2% FS with multipliers x1, x10, x100, x1k, x10k
Guard/ground load return:Yes
Megohmmeter:Scaled 100 -1MΩ with multipliers of x0.1, x1, x10, x100, x1k
Controls
Voltage output:Continuously adjustable up to max. voltage
Saftey
Interlocks:Zero start and external interface
Protection:Surge and transient
Cable length
Output cable:6m EPR x-ray with alligator clamp
Ground lead:6m with alligator clamp
Return lead:6m with alligator clamp
Input line cord:3m
Ground stick:6m lead and clamp included
Size & Weight
Controls:356mm w x 279mm d x 356mm h, 15kg
HV Tank:330mm w x 368mm d x 775mm h, 68kg