Specifications
Input:120V, 60Hz, 10A or 230V, 50/60Hz, 5A (±1% input voltage regulator)*
Output:0 - 75kVdc, 10mA, negative polarity, positive ground
Duty:Continuous
Metering
Voltmeter:3.5", scaled 0-37.5/75kVdc, ±2% FS accuracy
Currentmeter:3.5", scaled 0-1.0µAdc, ±2% FS with multipliers x1, x10, x100, x1k, x10k
Guard/ground load return:Yes
Megohmmeter:Scaled 100 -1MΩ with multipliers of x0.1, x1, x10, x100, x1k
Controls
Voltage output:Continuously adjustable up to max. voltage
Saftey
Interlocks:Zero start and external interface
Protection:Surge and transient
Cable length
Output cable:6m shielded with alligator clamp
Ground lead:6m with alligator clamp
Return lead:6m with alligator clamp
Input line cord:3m
Ground stick:6m lead and clamp included
Size & Weight
Controls:356mm w x 279mm d x 457mm h, 31kg
HV Tank:Included in controls case
PTS-75(f) face
*Due to the ferro-resonant designed input voltage regulator, if an inverter is used for the voltage source it must produce a "true sine wave" output and not a "modified sine wave" (square wave). This model is input frequency sensitive: either 50Hz or 60Hz but not both. Please Specify when ordering.