Specifications
Input:120V, 60Hz, 10A or 230V, 50/60Hz, 5A
Output:0 - 80kVdc, 10mA, negative polarity, positive ground
Duty:Continuous
Metering
Voltmeter:3.5", scaled 0-40/80kVdc, ±2% FS accuracy
Currentmeter:3.5", scaled 0-1.0µAdc, ±2% FS with multipliers x1, x10, x100, x1k, x10k
Guard/ground load return:Yes
Megohmmeter:Scaled 100 -1MΩ with multipliers of x0.1, x1, x10, x100, x1k
Controls
Voltage output:Continuously adjustable up to max. voltage
Saftey
Interlocks:Zero start and external interface
Protection:Surge and transient
Cable length
Output cable:6m shielded with alligator clamp
Ground lead:6m with alligator clamp
Return lead:6m with alligator clamp
Input line cord:3m
Ground stick:6m lead and clamp included
Size & Weight
Controls:356mm w x 279mm d x 457mm h, 28kg
HV Tank:Included in controls case
PTS-80(F) face
** This model does not contain the ferro-resonant input voltage regulator circuit found in the PTS-37.5 & PTS-75. This model can be operated with a non-sine wave producing inverter.