The VLF-200CMF provides a 200kVac peak output voltage, suitable for performing VLF hipot tests on 138kV cable and as a voltage source for Tan Delta and Partial Discharge testing on 230kV cable. The controls offer all the features of our other VLF models along with VLF Cable Burning. Trailer mount optional.

VLF-3.75CM(f)
Specification
Input:230V, 50/60Hz, 80A peak
Output:0 - 200kVac peak, 100mA, 0.1/0.05/0.02Hz sinusoidal
Duty:Continuous
Load Rating: 0.75μF @ 0.1Hz, 1.5μF @ 0.05Hz, 3.75μF @ 0.02Hz
Cable burning:Yes
Metering:
Voltage:3.5", 0 - 200kVac peak, 2% FS accuracy
Charging Currentmeter:3.5", 0 - 200mAac peak 5% FS accuracyy
Load capacitance meter:0-6μF
Controls:
Data LoggerAutomatic
Test duration timer:User programmable
Controls
Output cable:None: bushing output
Size/Weight:
Controls:610mm h x 648mm w x 1803mm h, 295kg
HV Tank:1499mm w x 2362mm d x 2210mm h, 1678kg